Wind Load Calculation Steps — Directional Procedure (Chapter 27)
PRELIMINARY — NOT FOR CONSTRUCTION. All results are for educational and reference use only. Must be independently verified by a licensed Professional Engineer (PE) or Structural Engineer (SE) before use in any project.
Step 1: Determine basic wind speed V (mph) from Figure 26.5-1 for Risk Category
Step 2: Determine exposure category (B, C, or D)
Step 3: Compute velocity pressure qz or qh
Step 4: Apply pressure coefficients Cp or GCp
Step 5: Calculate design wind pressure p
Basic Wind Speed by Risk Category
ASCE 7-22 provides separate maps for each risk category:
| Risk Category | Use | Typical V (mph) — Coastal SE US | Typical V — Midwest | Typical V — Mountain West |
|---|---|---|---|---|
| I | Low hazard (agricultural) | 110âÃÂÃÂ130 | 90âÃÂÃÂ100 | 100âÃÂÃÂ110 |
| II | Standard (most buildings) | 120âÃÂÃÂ160+ | 95âÃÂÃÂ110 | 105âÃÂÃÂ120 |
| III | High hazard (schools, hospitals) | 130âÃÂÃÂ180+ | 100âÃÂÃÂ120 | 110âÃÂÃÂ130 |
| IV | Essential facilities | 140âÃÂÃÂ200+ | 105âÃÂÃÂ125 | 115âÃÂÃÂ135 |
Note: Coastal hurricane zones have dramatically higher wind speeds. Miami/South Florida: V âÃÂà160âÃÂÃÂ185 mph (Risk II). Use ASCE 7 Figure 26.5-1A/B/C for the authoritative values.
Exposure Categories
| Category | Description | Typical Location |
|---|---|---|
| B | Urban/suburban, trees, buildings up to 30 ft for âÃÂÃÂ¥ 1500 ft upwind | Most inland building sites |
| C | Open terrain, scattered obstructions < 30 ft for âÃÂÃÂ¥ 1500 ft | Open fields, coastlines > 1500 ft from ocean |
| D | Flat, unobstructed coastline, water surfaces | Ocean shorelines, lakefronts |
Exposure D produces the highest wind pressures; exposure B produces the lowest.
Velocity Pressure Equation
qz = 0.00256 ÃÂàKz ÃÂàKzt ÃÂàKd ÃÂàKe ÃÂàVÃÂò (lb/ftÃÂò)
Where:
Kz = velocity pressure exposure coefficient (Table 26.10-1)
Kzt = topographic factor (1.0 for flat terrain, up to 1.58 for hilltops)
Kd = wind directionality factor (0.85 for buildings, 0.95 for chimneys)
Ke = ground elevation factor (1.0 for z âÃÂä 6,000 ft; slight reduction above)
V = basic wind speed (mph)
Kz Exposure Coefficients (Table 26.10-1)
| Height z (ft) | Exposure B | Exposure C | Exposure D |
|---|---|---|---|
| 0âÃÂÃÂ15 | 0.57 | 0.85 | 1.03 |
| 20 | 0.62 | 0.90 | 1.08 |
| 25 | 0.66 | 0.94 | 1.12 |
| 30 | 0.70 | 0.98 | 1.16 |
| 40 | 0.76 | 1.04 | 1.22 |
| 50 | 0.81 | 1.09 | 1.27 |
| 60 | 0.85 | 1.13 | 1.31 |
| 70 | 0.89 | 1.17 | 1.34 |
| 80 | 0.93 | 1.21 | 1.38 |
| 100 | 0.99 | 1.26 | 1.43 |
| 120 | 1.04 | 1.31 | 1.48 |
| 160 | 1.13 | 1.39 | 1.55 |
| 200 | 1.20 | 1.46 | 1.61 |
Design Wind Pressure — MWFRS (Buildings)
For Enclosed and Partially Enclosed Buildings (Chapter 27)
p = q ÃÂàG ÃÂàCp âÃÂàqi ÃÂà(GCpi)
Where:
q = qz for windward wall, qh for leeward/side walls and roof
G = gust factor (0.85 for rigid buildings h/least dimension < 4 and n1 > 1 Hz)
Cp = external pressure coefficient (Table 27.3-1)
qi = qh for enclosed buildings; qz for partially enclosed
GCpi = internal pressure coefficient (ÃÂñ0.18 enclosed, ÃÂñ0.55 partially enclosed)
External Pressure Coefficients Cp — Walls (Table 27.3-1)
| Surface | Cp |
|---|---|
| Windward wall | +0.8 |
| Leeward wall (L/B = 0 to 1) | âÃÂÃÂ0.5 |
| Leeward wall (L/B = 2) | âÃÂÃÂ0.3 |
| Side walls | âÃÂÃÂ0.7 |
External Pressure Coefficients Cp — Roofs
| Roof Type | Wind Direction | h/L | Cp |
|---|---|---|---|
| Flat roof (ÃÂø < 10ÃÂð) | Normal to ridge | — | âÃÂÃÂ0.3 to âÃÂÃÂ0.7 (suction) |
| Gable (0âÃÂÃÂ5ÃÂð) | Normal to ridge | âÃÂä 0.25 | âÃÂÃÂ0.7 windward; âÃÂÃÂ0.4 leeward |
| Gable (10ÃÂð) | Normal to ridge | âÃÂä 0.25 | âÃÂÃÂ0.9/+0.2 windward; âÃÂÃÂ0.3 leeward |
| Gable (20ÃÂð) | Normal to ridge | âÃÂä 0.25 | âÃÂÃÂ0.5/+0.3 windward; âÃÂÃÂ0.2 leeward |
| Gable (30âÃÂÃÂ45ÃÂð) | Normal to ridge | any | +0.2 to +0.8 windward; âÃÂÃÂ0.2 leeward |
| Hip roof (20ÃÂð) | Normal to ridge | any | âÃÂÃÂ0.6 windward; âÃÂÃÂ0.5 leeward |
Components and Cladding (C&C) — Chapter 30
C&C pressures are generally higher than MWFRS because they apply to smaller tributary areas. Used to design roof panels, cladding, windows, and connections.
p = qh ÃÂà[(GCp) âÃÂà(GCpi)]
GCp = external pressure coefficient for C&C (from Figures 30.3-1 through 30.3-7)
Depends on: zone (1/2/3 interior/edge/corner), effective wind area, roof geometry
Effective wind area: The loaded area contributing to the force on a component.
- For structural members: span ÃÂÃÂ tributary width
- For cladding panels: span ÃÂÃÂ fastener spacing
C&C pressure is always higher in corners (Zone 3 >> Zone 2 > Zone 1).
Typical C&C Pressure Ranges (90 mph basic wind, Exposure C, h = 30 ft)
| Application | Net Pressure Range (psf) | Controls |
|---|---|---|
| Wall cladding, Zone 1 (interior) | ÃÂñ15âÃÂÃÂ20 | Inward pressure |
| Wall cladding, Zone 2 (edge) | ÃÂñ20âÃÂÃÂ30 | Outward suction |
| Roof cladding, Zone 1 | âÃÂÃÂ20 to +10 | Upward suction |
| Roof cladding, Zone 2 (perimeter) | âÃÂÃÂ30 to +10 | High uplift at edges |
| Roof cladding, Zone 3 (corner) | âÃÂÃÂ40 to +10 | Maximum uplift at corners |
| Skylights, windows | ÃÂñ20âÃÂÃÂ35 | Positive inward pressure |
Worked Example: Simple Office Building
Given: 2-storey office, 40 ft ÃÂÃÂ 60 ft plan, 25 ft eave height, flat roof, Chicago suburb
- Risk Category II âÃÂàV = 100 mph (approximately; verify with ASCE 7 map)
- Exposure B (suburban)
- Kd = 0.85, Kzt = 1.0, Ke = 1.0, GCpi = ÃÂñ0.18 (enclosed)
Velocity pressure at roof (z = 25 ft): qh = 0.00256 ÃÂà0.66 ÃÂà1.0 ÃÂà0.85 ÃÂà1.0 ÃÂà100ÃÂò = 14.3 psf
Windward wall pressure: p = 14.3 ÃÂà0.85 ÃÂà0.8 âÃÂà14.3 ÃÂà(âÃÂÃÂ0.18) = 9.7 + 2.6 = 12.3 psf (inward)
Leeward wall pressure (L/B = 60/40 = 1.5, interpolate Cp âÃÂàâÃÂÃÂ0.4): p = 14.3 ÃÂà0.85 ÃÂà(âÃÂÃÂ0.4) âÃÂà14.3 ÃÂà(0.18) = âÃÂÃÂ4.9 âÃÂà2.6 = âÃÂÃÂ7.5 psf (outward/suction)
Total lateral wind force on 25 ft ÃÂÃÂ 40 ft wall: F_wind = (12.3 + 7.5) ÃÂÃÂ 25 ÃÂÃÂ 40 = 19,800 lb = 19.8 kips per frame
Frequently Asked Questions
What is the difference between MWFRS and C&C? MWFRS (Main Wind Force Resisting System) loads are used to design the primary lateral system: moment frames, shear walls, diaphragms. C&C (Components & Cladding) loads apply to individual panels, windows, roof sheets, and their connections. C&C loads are higher than MWFRS for small tributary areas. Use MWFRS for frames and shear walls; use C&C for cladding, purlins, and facade elements.
Why are roof corner zones designed for higher pressures? Wind flow separates at building corners and eaves, creating vortices that generate intense suction in corners. C&C Zone 3 (corner) pressures can be 2âÃÂÃÂ3ÃÂàhigher than interior Zone 1 pressures. Corner and edge zones must use heavier fastening, thicker panels, or additional attachments compared to interior panels.
Is the basic wind speed in ASCE 7 a service-level or strength-level load? Wind speeds in ASCE 7-22 (and since ASCE 7-10) are at strength level (equivalent to the old 3-second gust speed multiplied by the sqrt of the load factor, approximately 1.6 for LRFD). For LRFD, apply wind load W with a 1.0 factor (LC4: 1.2D + 1.0W + L). For ASD, apply 0.6W to convert strength-level wind back to service level. ASCE 7-10 and 7-16 also used strength-level wind; they are superseded by 7-22 and provided here for historical context only. Pre-ASCE 7-10 editions used service-level wind speeds with a 1.6 load factor under LRFD.
Do I need to check wind uplift on roof beams? Yes. Roof purlins and beams must be checked for uplift (negative pressure creates net upward force on the roof structure). LRFD LC5: 0.9D + 1.0W is the governing combination for uplift. Dead load is reduced to 0.9 to find the minimum stabilizing force.
How does exposure category affect design wind pressure? Exposure category controls the velocity pressure exposure coefficient Kz, which directly scales the velocity pressure qz. At a roof height of 30 ft, Kz = 0.70 for Exposure B (suburban), 0.98 for Exposure C (open terrain), and 1.16 for Exposure D (coastal flat terrain). This means an Exposure D building at 30 ft experiences approximately 66% higher velocity pressure than the same building in Exposure B at the same height. Selecting the correct exposure category is therefore one of the most consequential steps in wind load calculation.
What is velocity pressure qz and how is it calculated? Velocity pressure qz is the dynamic pressure exerted by wind moving at speed V at height z, computed as qz = 0.00256 ÃÂàKz ÃÂàKzt ÃÂàKd ÃÂàKe ÃÂàVÃÂò (lb/ftÃÂò). The constant 0.00256 converts miles-per-hour wind speed to pressure using standard air density at sea level. Kz accounts for height-dependent wind speed profile, Kzt for topographic speed-up over hills, Kd for the reduced probability of the design wind speed occurring simultaneously from the worst-case direction, and Ke for slight air density reduction at high elevations. For a typical flat-terrain suburban building at 30 ft with V = 115 mph, qz âÃÂà0.00256 ÃÂà0.70 ÃÂà1.0 ÃÂà0.85 ÃÂà1.0 ÃÂà115ÃÂò âÃÂà20.2 psf.
ASCE 7-22 Wind Load Procedure (Chapter 26-30)
ASCE 7-22 provides a comprehensive framework for determining wind loads on buildings and other structures. The primary procedure for most buildings is the Directional Procedure (Chapter 27 for MWFRS, Chapter 30 for C&C).
Step-by-Step Procedure
Step 1: Determine Risk Category (Table 1.5-1)
| Risk Category | Building Type | Importance Factor |
|---|---|---|
| I | Agricultural, minor storage | 0.8* |
| II | Standard occupancy (offices, residential) | 1.0 |
| III | Assembly, schools, jails | 1.0 |
| IV | Essential facilities (hospitals, fire stations) | 1.0 |
*Applies to wind speed selection, not a separate factor for wind since ASCE 7-10.
Step 2: Determine Basic Wind Speed V (Figure 26.5-1/26.5-2)
Select V from the ASCE 7-22 wind speed maps. The wind speed corresponds to the 3-second gust speed at 33 ft height in Exposure C, with the following mean recurrence intervals:
| Risk Category | MRI (years) | Example V (midwest US) |
|---|---|---|
| I | 300 | 105-110 mph |
| II | 700 | 115-120 mph |
| III | 1700 | 125-130 mph |
| IV | 3000 | 130-140 mph |
Step 3: Determine Exposure Category (Section 26.7)
| Category | Description | Typical Kz at 30 ft |
|---|---|---|
| B | Urban, suburban, wooded terrain | 0.70 |
| C | Open terrain, grassland, water in hurricane-prone zones | 0.98 |
| D | Flat unobstructed terrain, water surfaces | 1.16 |
Step 4: Determine Topographic Factor Kzt (Section 26.8)
Kzt = (1 + K1k2k3)^2, where K1, K2, K3 depend on hill shape, height, and distance from crest. For flat sites, Kzt = 1.0.
Step 5: Determine Directionality Factor Kd (Table 26.6-1)
| Structure Type | Kd |
|---|---|
| Buildings (MWFRS) | 0.85 |
| Buildings (C&C) | 0.85 |
| Arched roofs | 0.85 |
| Chimneys and tanks | 0.90 |
| Solid signs | 0.85 |
| Open signs / lattice frameworks | 0.85 |
Step 6: Calculate Velocity Pressure qz
qz = 0.00256 * Kz * Kzt * Kd * Ke * V^2 (ASCE Eq. 26.10-1)
Where Ke is the ground elevation factor (Table 26.9-1): Ke = 1.0 for elevations up to 1,000 ft; Ke = 0.94 at 6,000 ft.
Velocity Pressure Calculation: Worked Example
Problem: An office building in Dallas, TX. Risk Category II. Exposure C (open terrain). Flat site. Building dimensions: 60 ft wide x 120 ft long x 40 ft tall.
Step 1: Risk Category II, V = 115 mph (from ASCE 7-22 Figure 26.5-1A)
Step 2: Exposure C, Kzt = 1.0 (flat site), Kd = 0.85, Ke = 1.0
Step 3: Calculate qz at roof height (z = 40 ft)
From ASCE 7-22 Table 26.10-1 for Exposure C:
Kz at 40 ft = 1.04 (interpolated)
qz = 0.00256 * 1.04 * 1.0 * 0.85 * 1.0 * 115^2
= 0.00256 * 1.04 * 0.85 * 13,225
= 0.00226 * 13,225
= 29.9 psf
Step 4: qz at 15 ft (lower portion)
Kz at 15 ft (Exposure C) = 0.85
qh = 0.00256 * 0.85 * 1.0 * 0.85 * 1.0 * 115^2 = 24.4 psf
Step 5: Design pressures (MWFRS, enclosed building, h = 40 ft)
Using ASCE 7-22 Figure 27.3-1 (enclosed simple diaphragm):
Windward wall: p = qz * GCp - qi * GCpi = 29.9 * 0.85 - 29.9 * (+/-0.18)
Positive (inward): 25.4 - 5.4 = 20.0 psf (with +0.18 internal)
Negative (outward): 25.4 + 5.4 = 30.8 psf (with -0.18 internal)
Leeward wall: p = qh * GCp - qi * GCpi
Suction: qh * (-0.5) = 24.4 * (-0.5) = -12.2 psf (external)
With internal: -12.2 +/- 5.4 = range of -6.8 to -17.6 psf
Roof (flat): qh * GCp
Zone 1 (interior): 24.4 * (-0.9) = -22.0 psf (suction)
Zone 2 (edge): 24.4 * (-1.6) = -39.0 psf (suction)
Zone 3 (corner): 24.4 * (-2.2) = -53.7 psf (suction)
These pressures are combined in LRFD load combinations (1.0W for wind) to design the MWFRS members. The roof corner Zone 3 pressure of 53.7 psf suction is more than double the interior Zone 1 pressure, demonstrating why corner zone detailing requires special attention.
Run This Calculation
âÃÂàWind Load Calculator — ASCE 7 / AS 1170.2 wind pressure calculation for MWFRS and components & cladding.
âÃÂàLoad Combinations Calculator — combine wind loads with dead and live loads using ASCE 7 LRFD or ASD load factors.
âÃÂàPortal Frame Calculator — rafter and column design for portal frames under combined gravity and wind loading.
Try it now: Check your wind load with our free Wind Load calculator âÃÂÃÂ
Related pages
- Load Combinations ASCE 7 — how wind fits into LRFD/ASD load combinations
- Snow Load Calculation — companion gravity load for roof design
- Steel Beam Span Guide — span capacity under combined gravity + wind
- Column Compression Strength Tool — combined axial + bending under wind
- Deflection Limits Reference — lateral drift limits for wind design
- Reference tables directory
- How to verify calculator results
- Seismic Design Categories
- Floor Live Load Reference
- Steel Roof Framing Reference
- snow load calculator
Wind loads per ASCE 7-22 Chapters 26âÃÂÃÂ31. Basic wind speed must be determined from the project site using ASCE 7 Figure 26.5-1. Local jurisdictions may adopt modified wind speed maps. Always verify with the authority having jurisdiction.
Disclaimer (educational use only)
This page is provided for general technical information and educational use only. It does not constitute professional engineering advice, a design service, or a substitute for an independent review by a qualified structural engineer. Any calculations, outputs, examples, and workflows discussed here are simplified descriptions intended to support understanding and preliminary estimation.
All real-world structural design depends on project-specific factors (loads, combinations, stability, detailing, fabrication, erection, tolerances, site conditions, and the governing standard and project specification). You are responsible for verifying inputs, validating results with an independent method, checking constructability and code compliance, and obtaining professional sign-off where required.
The site operator provides the content "as is" and "as available" without warranties of any kind. To the maximum extent permitted by law, the operator disclaims liability for any loss or damage arising from the use of, or reliance on, this page or any linked tools.
Design Resources
Calculator tools
Design guides